PCAN-Ethernet Gateway DR
Two CAN buses tunnelled over your IP network, on a DIN rail
PCAN-Ethernet Gateway DR joins CAN segments that sit far apart by carrying their frames across an ordinary LAN. Each CAN frame is packed into a TCP or UDP packet and delivered to a second gateway, or to PC software, at the other end. The unit has one RJ-45 network port and two High-speed CAN channels in a 22.5 mm plastic case for DIN rail mounting, and it is rated for -40 to 85 C.
Setup is done in a web interface, which also adapts to mobile screens: bit rates, IPv4 address, routes between CAN and LAN, and ID filters for 11-bit and 29-bit frames. A JSON interface over HTTP lets your own software read device, route and filter status. Its write access is switched off on delivery.
Highlights
- 2 High-speed CAN channels and one 10/100 Mbit/s LAN port
- CAN frames carried over TCP or UDP
- Galvanic isolation up to 500 V
- Web interface for routes, filters, updates and backup
- JSON interface for software access
- DIN rail casing, 8 to 30 V supply, -40 to 85 C
Versions
- IPEH-004010: PCAN-Ethernet Gateway DR in DIN rail plastic casing
Software
- Web interface: configuration import and export, firmware update, reboot, factory reset and a scan for other PCAN-Gateways on the network
- JSON interface over HTTP GET, with a built-in shell view and documentation
- Virtual PCAN-Gateway for Windows 11 (x64/ARM64) and 10 (x64)
- Sample code and a Wireshark dissector for socket development
Key Specifications
| Spec | Value |
|---|---|
| Order number | IPEH-004010 |
| CAN | 2 x High-speed CAN (ISO 11898-2), CAN 2.0 A/B |
| Bit rates | 5 kbit/s to 1 Mbit/s, listen-only mode available |
| Transceiver | TJF1441AT |
| LAN | 10/100 Mbit/s, TCP or UDP, RJ-45 with status LEDs |
| Isolation | Up to 500 V between the CAN channels and against RS-232 and supply |
| Connectors | 4-pole Phoenix screw terminals for CAN, RS-232 (reserved for future use) and power |
| Supply | 8 to 30 V |
| Casing | Plastic, 22.5 mm wide, DIN rail (EN 60715 TH35) |
| Operating temperature | -40 to 85 C |
In the Box
- PCAN-Ethernet Gateway DR
- Mating connectors for both CAN channels, RS-232 and power
- RJ-45 network patch cord, 2 m
- Printed quick start guide
- Manual (PDF)
For CAN FD, see the PCAN-Ethernet Gateway FD DR; to connect D-Sub cabling, the PCAN-Adapter D-Sub for DR Products.
For quantities, lead time or a quote, contact Pertech.